NAMEbicker_ser - Driver for Bicker DC UPS via serial port connections SYNOPSISbicker_ser -h bicker_ser -a UPS_NAME [OPTIONS] Note This man page only documents the hardware-specific features of the bicker_ser driver. For information about the core driver, see nutupsdrv(8). SUPPORTED HARDWAREbicker_ser supports all Bicker UPSes shipped with the PSZ-1053 extension module such as UPSIC-1205, UPSIC-2403, DC2412-UPS and DC2412-UPS-LD. CABLINGThe needed cable is a standard pin-to-pin serial cable with pins 2, 3 and 5 (on DB9 connector) connected. EXTRA ARGUMENTSThis driver supports no extra arguments from ups.conf(5). VARIABLESDepending on the type of your UPS unit, some of the following variables may be changed with upsrw(8). If the driver can’t read a variable from the UPS, it will not be made available. Whenever not explicitly stated, any variable can be disabled, in which case the action it performs will not be executed. To disable a variable, set it to an empty value. ups.delay.shutdown (in seconds, default disabled) If activated and the UPS is in battery mode and the set
time has expired, the output will be disabled, and the UPS and energy storage
will be disconnected.
ups.delay.start (in seconds, default disabled) If activated and a restart condition switches the UPS
output off and on again, the set time is the delay between switching on and
off. The time should cause a defined off time so that capacities in the
application can be discharged.
battery.charge.restart (in percent, default disabled) If activated and the UPS is off or restarts, the UPS
output will not be released until the energy storage device has the set charge
state. The energy storage device is charged in the meantime.
battery.charge.low (in percent, default 20) If activated and the UPS is in battery mode and the
battery level drops below the set value, a shutdown command via relay event is
signaled.
experimental.output.current.low (in mA, default 200) If activated and the UPS is in battery mode and the
current drops below the set value, the output of the UPS will shut down and
disconnect the energy storage to prevent self-discharge.
experimental.ups.delay.shutdown.signal (in seconds, default disabled) If activated and the UPS is in battery mode and the set
time has elapsed, a shutdown command via relay event is signaled.
experimental.ups.delay.shutdown.signal.masked (in seconds, default disabled) If activated and the UPS is in battery mode and the
signal at the IN-1 input is high and the set time has expired, a shutdown
command via relay event is signaled.
experimental.battery.charge.low.empty (in percent, default 20) This parameter stores the threshold value for the
"Battery Empty" signal. Currently this setting is only valid for
relay signaling. Cannot be disabled.
experimental.ups.relay.mode (default 0x01) This parameter controls the behavior of the relay in case
of different events. Cannot be disabled.
Available relay modes:
INSTANT COMMANDSshutdown.return Turn off the load and return when power is back.
KNOWN ISSUES AND BUGSups.delay.shutdown is not honored Although that delay is properly set when sending the
shutdown command, it seems some UPS ignore it and use a fixed 2 seconds delay
instead.
AUTHORNicola Fontana <ntd@entidi.it> SEE ALSOThe core driver:nutupsdrv(8) Internet resources:The NUT (Network UPS Tools) home page: https://www.networkupstools.org/
|