Namemodbus_send_raw_request - send a raw request Synopsisint modbus_send_raw_request(modbus_t *ctx, const uint8_t *raw_req, int raw_req_length); DescriptionThe modbus_send_raw_request() function shall send a request via the socket of the context ctx. This function must be used for debugging purposes because you have to take care to make a valid request by hand. The function only adds to the message, the header or CRC of the selected backend, so raw_req must start and contain at least a slave/unit identifier and a function code. This function can be used to send request not handled by the library. The public header of libmodbus provides a list of supported Modbus functions codes, prefixed by MODBUS_FC_ (eg. MODBUS_FC_READ_HOLDING_REGISTERS), to help build of raw requests. Return valueThe function shall return the full message length, counting the extra data relating to the backend, if successful. Otherwise it shall return -1 and set errno. Examplemodbus_t *ctx; /* Read 5 holding registers from address 1 */ uint8_t raw_req[] = { 0xFF, MODBUS_FC_READ_HOLDING_REGISTERS, 0x00, 0x01, 0x0, 0x05 }; int req_length; uint8_t rsp[MODBUS_TCP_MAX_ADU_LENGTH]; ctx = modbus_new_tcp("127.0.0.1", 1502); if (modbus_connect(ctx) == -1) { See also
|